26
Input range -200 ... +800 °C adjustable using
DIP switches
Offset input range up to +25 % possible
Output
Voltage output 0 ... 10 V
Load resistance 1 k
Accuracy
Measurement range accuracy
100 K; < 600 K;
ϑ
min
-100 °C ± 0.1 from measurement range
100 K ± 0.1 K
600 K ± 0.2 % from measurement range
Temperature coefficient
Measurement range
200 K 200 ppm/K (typ. 80 ppm/K)
100 K; < 200 K 225 ppm/K (typ. 90 ppm/K)
40 K; < 100 K 450 ppm/K (typ. 180 ppm/K)