23
AL1-4
Alarms 1- 4 enable/disable menu
1 & 2
Select
A12y
A12n
Alarms one and two enabled
Alarms one and two disabled
Toggle Accept
3 & 4
Select
A34y
A34n
Alarms three and four enabled
Alarms three and four disabled
Toggle Accept
Press PGM to skip to analogue output menu.
AL1
Alarm channel setup menus (repeated for each enabled alarm channel)
Coil state
A1nE
A1nd
Normally energised
Normally de-energised
Toggle Accept
Alarm
type
A1=lO
a1=HI
a1=OC
A4=Sr
A4=gr
Low alarm
High alarm
Open circuit alarm (ch 1 only)
Siren alarm (ch 4 only)
Group alarm (ch 4 only)
Toggle Accept
Note: the following settings are not shown for group siren or sensor break alarms
Setpoint
SP1=
50.0
Introduces setpoint value
Any value witin the display limits
-
Inc
-
Dec
Next
Accept
Deadband
db1=
10.0
Introduces deadband value
Any value within the display span
-
Inc
-
Dec
Next
Accept
Timer
delay
dl1=
Introduces timer delay - - Next
0
(0s to 4200 s) Inc Dec Accept
AL2 , AL3 , AL4
Alarm Channel two, three and four setup menus
A-ALL
All Alarms Submenu (reset mode and setpoint security settings)
Reset
sequence
nor
reS
Automatic reset
Manual reset
Toggle Accept
Setpoint
security
SECy
SECn
Change setup mode only
Change in run or setup mode
Toggle Accept
Setup Sequence (continued)