Power Supply Requirements
Check the power supply against the model number before applying
power to the instrument. Units must be used with the specified mains
supply, ratings are as follows:
Voltage Range Nominal Voltage Power Frequency
100–132 V AC 110 V AC 6 VA 47-63 Hz
200264 V AC 240 V AC 6 VA 47-63 Hz
12–50 V DC* 24 V DC 5 W (at 24 V DC) -
*Using a DC power supply that provides this voltage will comply with
the instrument’s UL/CSA listing.
Connections
Strip wires to 7 mm from the ends. Use a suitable ferrule for multi-
stranded wires (do not solder).
Use 12-28 AWG Cu Wire rated for temperatures above 70 °C Only,
tighten to 4.5 lb-In.