Weidmuller XFAR - Universal glavanically isolated signal conv Manuale Utente Pagina 18

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 28
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 17
18
For effective protection from electromagnetic noise, all signal cables
must be shielded, or located on conductive trays or in conduits.
Terminal Signal
1
24 V DC (out)
Input signals
2
Current +
3
Common
4
Voltage +
5
Alarm Channel One Inhibit
Alarm inhibit
Signals
6
Alarm Channel Two Inhibit
7
Inhibit Input Common
8
Link to Terminal 1 to change the set-up Security Link
9 Neutral (−)
Power supply
10 Live (+)
11 Normally Closed
Alarm Channel One
12 Common
13 Normally Open
14 Normally Closed
Alarm Channel Two
15 Common
16 Normally Open
Case Earthing is via a stud on lower side of case
The double lines represent isolation between circuits
Inhibit Input Signals
The alarm inhibit inputs accept voltages. A 4-40 V signal will prevent
the alarm channel from operating. Voltages >3 V will allow the alarm to
operate normally.
Vedere la pagina 17
1 2 ... 13 14 15 16 17 18 19 20 21 22 23 ... 27 28

Commenti su questo manuale

Nessun commento

Vermont Casting Krby uživatelské příručky

Začínající na C

Klepnutím na abecedu níže přejděte na úplný seznam modelů začínajících tímto písmenem

Modely Typ Dokumentu
ChateauTM DVT38IN
Uživatelský manuál   Vermont Casting ChateauTM DVT38IN User's Manual, 48 stránky